Naidian White Color 12V 24V Digital Time Relay NDS8-2Z

Short Description:

DH48S Series Digital time relay, is on-delay type. Applicable to the circuit of 50/60Hz, operating voltage up to AC380V as a delay component to connect or break the circuit as per presetting time. This series comply with the standard of Q/ZND 1011-2000, GB14048.5 and JB/T10047-999.


Product Detail

Product Tags

DH48S Series Digital Time Relay Instruction

● General

DH48S Series Digital time relay, is on-delay type. Applicable to the circuit of 50/60Hz, operating voltage up to  AC380V as a delay component to connect or break the circuit as per presetting time.

This series comply with the standard of Q/ZND 1011-2000, GB14048.5 and JB/T10047-999.

● Technical Data

Type

DH48S-1Z

DH48S-2Z

NDS8C-2

DH48S-S

Rated voltage

AC380V, 220V, 127V, 110V, 36V, 24V, 50Hz ; DC24V

Operating type

On-delay

Cycle delay

Timing range

0.01s~99.99s; 1s~99min99s;1min~99h99min

1s~99s;1min~99min;1h~99h;0.1s~9.9s;

0.1min~9.9min;0.1h~9.9h,1min~99min;10h~99h

Repeated errors

≤1%

Contact quantity

 On-delay 1C

 On-delay 2C

On-delay 1C

instantaneous contact 1C

“1” On-delay 1C

“2” On-delay 2C

Contact capacity

AC250V 5A  COSФ=1; DC24V 7A

Mechanical life

1×106

Electric Life

1×105

Mounting type

Screw mounting or 35mm rail

● Wiring Diagram

481
482

● Outline Dimension

483
484

● Notice

1) Please preset the delaying time before power on due to the time relay possesses the function of record, the interval time of restarting relay is 0.5s.

2) Please set the dial to the time you want, connect the power source, then the LED screen starts to timing, when reach up to preset time, delay contact change to stop timing to complete timing control.

3) Reset function: Please connect the reset terminal  at anytime, the relay recover to the initial state.

4) Pause function: Please connect the pause terminal  at anytime, then stopping timing and keep the current time ,when disconnect the terminal, then the relay continue to timing.

5) Please adopt the shield lead line, when the lead line connected the reset terminal or connected the pause terminal are too long under the environment of high electric filed.

6) Don’t input the voltage to  the reset terminal, pause terminal. Unless damage the relay.

Product Application

pro_09

Production Process

pro_13

EXhibiton

pro_15

Certification

pro_17

Packaging & Shipping

pro_19-1

  • Previous:
  • Next:

  • Write your message here and send it to us